In calculating large rain water drain pipe must be known that rainwater roof is in the area of m2.
As standard discharge pipe sizes are as follows:
- Diameter 3 ", volume 255 liters / min
- Diameter 4 ", volume 547 liters / min
- Diameter 5 ", volume 990 liters / min
- Diameter 6 ", volume 1610 liters / min
- Diameter 8 ", volume 3470 liters / min
As the following example we present a case as follows:
Egg a building has a roof area of 1,000 m2. How the amount of pipe and the amount of rain water pipes needed on the roof of the building?
Answer:
- Roof area = 1,000 m2.
- The average rain - we take the average in Indonesia between = 5-8 liters / minute.
- Precipitation = 1,000 m2 x 5-8 liters / minute = 5000-8000 liters / minute. (taken 8000 liters / min)
- Gutter used a diameter of 6 "(volume 1610 liters / min)
- If precipitation = 8,000 liters / minute, the rain water will flow down within 1 minute is = 8.000: 1.610 = 4.97 fruit
Thus it seems, may be useful and thank you.